Refrigeration units of provision storerooms for storage of sausage, ham products and edible animal fats
Section 6
Main elements of refrigeration unit of storeroom for storage of sausage and ham products
6.1 Condensing unit Bitzer LH44/2FC-2.2Y-40S

Figure 6.1 – Unit overall and connection dimensions
Positional designations given in figure 6.1:
1 – suction line connection;
2 – discharge pipeline;
3 – liquid refrigerant pipeline;
4 – connection of liquid refrigerant line at receiver outlet;
5 – connection of refrigerant emergency discharge valve 1 ¼-12 UNF.
Unit technical characteristics
Table 6.1
|
Parameter name |
Value |
| Weight |
80 kg |
| Total width |
650 mm |
| Total depth |
607 mm |
| Total height |
516 mm |
| Suction line connection |
16 mm – 5/8” |
| Discharge line connection |
10 mm – 3/8” |
| Fans quantity |
1 pc. |
| Voltage (Standard) |
230 V – 1 ph – 50 Hz |
| Fan consumption current |
0,56 A |
| Fan consumption power |
125 W |
| Air volume flow rate |
1840 m³/h |
| Condensing unit volume |
2,5 dm³ |
| Receiver type |
FS056 |
| Maximum filling-up with refrigerant R507 90% at 20 °С |
5,4 kg |
| Sound power level (-10°C/45°C) @ 50Hz |
73,5 dB(A) |
| Sound pressure level @1m (-10°C/45°C) @50Hz |
65,5 dB(A) |
Technical characteristics of condensing unit at nominal mode, as applied to refrigeration unit of provision storeroom for storage of sausage and ham products, are given in Table 6.2.
Table 6.2
|
Parameter name |
Value |
| Unit type |
LH44/2FC-2.2Y-40S |
| Series |
Standard |
| Refrigerant |
R507 |
| Boiling temperature of evaporation refrigerant |
-11°C |
| Ambient temperature |
35°C |
| Suction vapours temperature |
20°C |
| Power supply |
400 V – 3 ph – 50 Hz |
| Effective overheating |
100% |
| Capacity regulator |
100% |
| Refrigeration capacity |
4,02 kW |
| Evaporator refrigeration capacity |
4,02 kW |
| Consumption power |
2,41 kW |
| Current (400 V) |
4,29 A |
| Power supply voltage |
380-420 V |
| Refrigerant mass flow rate |
129,1 kg/h |
| Condensation temperature SCT |
50,3 °C |
| Liquid overcooling |
3,00 K |
| Operation mode |
Standard |
Figure 6.2 – Graph of application field
Designations given in Figure 6.2:
tc – condensation temperature
t0 – boiling temperature
t0h –suction vapours temperature
Х – point of nominal mode
6.2 Air cooler ECO MIC 300 ED

Figure 6.3 – Overall and connection dimensions of air cooler
Technical characteristics of air cooler
Table 6.3
|
Parameter name |
Unit of measurement |
Value |
| Model |
- |
MIC 300 ED |
| Nominal refrigeration capacity |
kW |
1,99 |
| Air flow rate |
m3/h |
1380 |
| Jet range |
m |
2×2,5 |
| Inner heat-exchange surface |
m2 |
1,3 |
| Outer heat-exchange surface |
m2 |
11,8 |
| Fans quantity |
pcs. |
3 |
| Fan diameter |
mm |
230 |
| Fans consumption current |
A |
1,05 |
| Fan consumption power |
W |
159 |
| Refrigerant volume |
dm3 |
3 |
| Power consumed by electrical defrosting system |
W |
2400 |
| Heat exchanger connections | ||
| Refrigerant inlet (SAE) |
inch |
1/2 |
| Refrigerant outlet |
mm / inch |
22 / 7/8 |
| Drainage |
- |
G 1/2 |
| Weight |
kg |
19 |