Refrigeration units of provision storerooms for storage of sausage, ham products and edible animal fats
Section 8
Main elements of refrigeration unit of storeroom for storage of edible animal fats
8.1 Condensing unit Bitzer LH64/2CC-3.2Y-40S

Figure 8.1 – Unit overall and connection dimensions
Positional designations given in figure 6.1:
1 – suction line connection;
2 – discharge pipeline;
3 – liquid refrigerant pipeline;
4 – connection of liquid refrigerant line at receiver outlet;
5 – connection of refrigerant emergency discharge valve 1 ¼-12 UNF.
Unit technical characteristics
Table 8.1
|
Parameter name |
Value |
| Weight |
129 kg |
| Total width |
1000 mm |
| Total depth |
672 mm |
| Total height |
687 mm |
| Suction line connection |
22 mm – 7/8” |
| Discharge line connection |
12 mm – 1/2” |
| Fans quantity |
1 pc. |
| Voltage (Standard) |
230 V – 1ph – 50 Hz |
| Fan consumable current |
1,41 A |
| Fan consumable power |
301 W |
| Air volume flow rate |
3884 m³/h |
| Condenser volume |
5,3 dm³ |
| Receiver type |
FS076 |
| Maximum filling-up with refrigerant R507 90% at 20 °С |
7,5 kg |
| Sound power level (-10°C/45°C) @50Hz |
79,5 dB(A) |
| Sound pressure level @1m (-10°C/45°C) @50 Hz |
71,5 dB(A) |
Technical characteristics of condensing unit at nominal mode, as applied to refrigeration unit of provision storeroom for storage of sausage and ham products, are given in Table 8.2.
Table 8.2
|
Parameter name |
Value |
| Unit type |
LH64/2CC-3.2Y |
| Series |
Standard |
| Refrigerant |
R507 |
| Refrigerant boiling temperature |
-15 °C |
| Ambient temperature |
35 °C |
| Suction vapours temperature |
20 °C |
| Power supply |
400 V – 3ph – 50 Hz |
| Effective overheating |
100% |
| Capacity regulator |
100% |
| Refrigeration capacity |
6,59 kW |
| Evaporator refrigeration capacity |
6,59 kW |
| Consumable power |
3,63 kW |
| Current (400 V) |
6,52 A |
| Power supply voltage |
380-420 V |
| Refrigerant mass flow rate |
198,8 kg/h |
| Condensation temperature SCT |
46,6 °C |
| Liquid overcooling |
3,00 K |
| Operation mode |
Standard |

Figure 8.2 – Graph of application field
Designations given in the figure:
tc – condensation temperature;
t0 – boiling temperature;
t0h – suction vapours temperature;
Х – point of nominal mode.
8.2 Air cooler ECO CTE 58M6 ED

Figure 8.3 – Overall and connection dimensions of air cooler ECO CTE 58M6 ED
Technical characteristics of air cooler
Table 8.3
|
Parameter name |
Unit of measurement |
Value |
| Model |
- |
CTE 58М6 |
| Nominal refrigeration capacity |
kW |
3,02 |
| Air flow rate |
m³/h |
1500 |
| Jet range |
m |
9 |
| Ribs pitch |
mm |
6,0 |
| Inner heat-exchange surface |
m² |
2,1 |
| Outer heat-exchange surface |
m² |
13,3 |
| Heat exchanger connections | ||
| Refrigerant inlet (SAE) | inch |
1/2 |
| Refrigerant outlet | mm / inch |
22 / 7/8 |
| Drainage |
- |
G 1 |
| Weight |
kg |
27,4 |
| Fans quantity |
pcs |
2 |
| Fan diameter |
mm |
250 |
| Fans consumable current |
A |
0,94 |
| Fans consumable power |
W |
150 |
| Refrigerant volume |
dm³ |
4,34 |
| Power consumed by electrical defrosting system |
W |
1275 |